The fouling factor is important for the selection of an evaporator. The value Onda suggest to input in selection software are:
For evaporators:
- Normal water in closed circuit: 0,000043 m2K/W;
- Water in open circuit: 0,000086 m2K/W;
- Solutions with glycol <40%: 0,000086 m2K/W;
- Solutions with glycol >40%: 0,000172 m2K/W.
For condensers:
- Normal city water: 0,000043 m2K/W;
- Treated tower water: 0,000043 m2K/W;
- River water: 0,000086 m2K/W;
- Solutions with glycol <40%: 0,000086 m2K/W;
- Solutions with glycol >40%: 0,000172 m2K/W.